LIST OF MAJOR PLANT EQUIPMENTS

No. Name Type Manufacturer Function – General parameters
1 Micro-ohm Meter ACCU-OHM-S2 Vanguard Instruments – USA Test current range: 10 Amperes – 200 AmperesResistance reading range: 1 microhm – 300 miliohms
2 Transformer Winding Resistance Test Set WRM10 Vanguard Instruments – USA Test current range: 10 Amperes maximum. Test voltage: 36 Vdc maximum.Resistance reading range: 1 microhm – 2000 ohms
3 Current Transformer Set EZCT-2000 Vanguard Instruments – USA Saturation Test. Output test voltage from 50, 300, 500, 1200 and 2000 Volts.CT Ratio and Polarity Test. Turn ratio range: 0.8 – 5000.CT Winding Resistance Test. Resistance reading range: 100 microhm – 10 ohms.
4 Digital Transformer Ratio meter DTR8500 AEMC – USA Testing ratio of VT, PT and CT. Displaying polarity and excitation current. Ratio range: 0.8 – 1500.Excitation signal: PT/VT mode: 44Vrms maximum. CT mode: 0 – 1 A Auto Level, 0.1 – 5 Vrms.Excitation current display: Range: 0 – 1000 mA.
5 AC/DC High Voltage Set AИД-70/50 Harkovenergopribor Electrical – UKRAINE High Voltage DC to 70 kV, current to 12 mA.High Voltage AC to 50 kV, current to 20 mA.
6 Protective Relay Tester MPRT 8415 Megger – USA Testing all types of 3 phases relay .Power 800 VA. Output-Current/Max (Amperes/Volts): 16/50; 30/26,7; 60/13,4.
7 Insulation Oil Purifier ZYD-50 Chonqing Zhongneng Oil Manufacture – CHINA Remove the free water, soluble water, gas, acid, free carbon and other impurities high-efficiently Capacity: 3000 l/h. Water content of the treated oil is ≤ 3 PPM and gas content ≤ 0.1 %.
8 Vacuum Motor-Pump THV Maxei – France Flow in m3/h: 170. Limit vacuum in mbars: 0.08
9 Oil Treatment Arras – Maxei THV-4000 Maxei – France Remove the free water, soluble water, gas, acid, free carbon and other impurities high-efficiently Capacity: 4000 l/h. Filtration by cartridges in nominal µm: 1. Limit vacuum against closed suction in mbars: 0.08. Vacuum during treatment in mbars: 0.5 – 2.
10 Tank of Oil Viet Nam Capacity: 20m3